ESCAPE ROUTES
Corridors, exits, stairways and ramps: helping people identify and follow an evacuation route.
TRE C / INTEGRATED SOLUTIONS · SAFETY
Building safety can be considered from the earliest architectural design stage. TRE C offers LED solutions with an emergency function for integration into its metal suspended ceilings, configured to suit each project.
LED + BATTERY BACKUP
THE PURPOSE
If the normal lighting supply is interrupted, a properly designed emergency lighting installation helps occupants orient themselves, identify obstacles and reach an escape route.
An emergency luminaire is more than a light fitted with a battery: its position, light distribution, response time and duration must be appropriate for the space.
Corridors, exits, stairways and ramps: helping people identify and follow an evacuation route.
Open-plan spaces and shared areas: providing visibility so occupants can reach an escape route.
Potentially hazardous tasks: allowing a process to be stopped or made safe as required.
OPERATING PRINCIPLE
A self-contained unit may combine an LED light source with emergency control gear and a rechargeable battery. The exact design depends on the selected components.
The driver supplies the LED according to the selected operating mode, while the battery is kept charged.
The emergency circuitry detects loss of the normal supply and powers the LED from the battery.
Normal operation resumes and the battery is recharged.
The two operating arrangements serve different needs and must be supported by the selected luminaire.
The light source used for emergency operation is normally off and switches on when the normal supply fails.
The light source operates during normal use and continues to provide its intended function under emergency conditions.
DESIGN DATA
UNI EN 1838:2025 specifies the illuminance required in designated areas, not a fixed lumen output for each luminaire. Compliance must be assessed through lighting design.
| Application | General lighting requirement | Duration |
|---|---|---|
| Escape routes up to 2 m wide | At least 1 lx at floor level across the central band, half the route width. | At least 1 hour for emergency escape lighting. |
| Open areas / anti-panic | At least 0.5 lx at floor level, subject to the assessment areas defined by the standard. | At least 1 hour for emergency escape lighting. |
| High-risk task areas | At least 10% of the normal maintained illuminance, and never below 15 lx on the task area. | Based on the time needed to bring the activity to a safe condition. |
These figures are an introductory summary. Building use, fire-safety rules and risk assessments may require higher illuminance levels or longer durations. The design must also assess distribution, uniformity, glare and performance depreciation.
Lumens (lm) measure the light output of a luminaire. Lux (lx) measure the light reaching a surface. The number of luminaires depends on emergency-mode light output, optics, installation height and room geometry.
TECHNICAL FRAMEWORK
System design and compliance depend on the building and applicable national rules. Key references include:
Lighting requirements for emergency escape routes, open areas and high-risk task areas.
Emergency escape lighting systems: installation, documentation, inspection, testing and maintenance.
Particular safety requirements for luminaires intended for emergency lighting.
Requirements relevant to Italian workplaces and buildings, including the Ministerial Decree of 3 August 2015 where applicable.
Compliance of a luminaire and compliance of a complete lighting installation are separate matters. Electrical design, installation and mandatory checks must be carried out by the responsible professionals.
TRE C SOLUTIONS
TRE C can assess the supply of LED modules with an emergency function integrated into its metal ceiling systems. Panel geometry, housings, component access and electrical interfaces can be coordinated within the project.
Light points planned in line with panel modules and the ceiling layout.
Selection and verification of LED source, emergency driver, battery, optics and required duration.
Working with electrical designers and installers to define provisions and the information required for compliance checks.
DALI control of normal lighting is separate from emergency operation. Automatic testing, centralised monitoring and emergency control require suitable compatible equipment and must be specified in the design.
Performance of the complete configuration, including emergency light output, duration and applicable conformity, is defined and documented for the actual solution offered. No particular battery duration or certification is implied for every variant.
FREQUENT QUESTIONS
No. 1 lux is an illuminance level on a reference surface, not the light output of a luminaire. Quantity and positions require lighting calculations.
No. One hour is a general minimum for emergency escape lighting; some applications require a longer duration.
No. Compatibility of the LED and control gear, thermal conditions, accessibility and compliance of the complete configuration must be checked.
DESIGN WITH TRE C
Share the ceiling system, room dimensions and emergency lighting requirements. We will assess the feasible configuration and available technical documentation.